Artificial Intelligence Notice: ISA prohibits the entry of ISA standards and related ISA intellectual property (“ISA IP”) into any form of Artificial Intelligence (AI) tools, such as ChatGPT. Additionally, creating derivatives of ISA IP using AI is also prohibited without express written permission from ISA’s CEO. In the case of such use, ISA will suspend a licensee’s access to ISA IP, and further legal action will be considered. Please review ISA's Terms and Conditions for further information.

  • CCST
ISA Certified Control Systems Technician (CCST) program

Certified Control System Technicians (CCSTs) calibrate, document, troubleshoot, and repair/replace instrumentation for systems that measure and control level, temperature, pressure, flow, and other process variables.

CCST question

When connecting a "K" type thermocouple to a control system where extension wires are required, it is important to use only properly installed "KX" extension wires because:

A. this prevents the formation of a second temperature measurement junction.
B. the manufacturer's warranty for the thermocouple would be voided if "KX" extension wire is not used.
C. "KX" thermocouple extension wire comes with special connectors for making the connection.
D. "KX" thermocouple extension wire is cheaper than "JX" thermocouple extension wire and reduces installation cost.

CCST Answer

The correct answer is A; it prevents the formation of a second temperature measurement junction. A thermocouple measurement junction is formed wherever two dissimilar metals are joined. KX-type thermocouple extension wire is made of the same metals as the K-type thermocouple (chromel and alumel). When extending the thermocouple leads with an extension wire back to the control system input card, KX thermocouple extension wire must be used, and the chromel wire and the alumel wire must be joined to the wire of the same metal in the extension cable. If JX or another type of extension wire is used, another measurement junction is formed. For instance, if JX extension cable is used in the example in this problem, the point where the iron and chromel wires are joined would form another thermocouple. This will negatively affect the intended measurement signal.

Proper installation of thermocouple extension wires also requires special terminal blocks to prevent additional junctions from being formed.

Reference: Goettsche, L.D. (Editor), Maintenance of Instruments and Systems, Second Edition, ISA, 2005.

Reader Feedback


We want to hear from you! Please send us your comments and questions about this topic to InTechmagazine@isa.org.



Like This Article?

Subscribe Now!

About The Author