Artificial Intelligence Notice: ISA prohibits the entry of ISA standards and related ISA intellectual property (“ISA IP”) into any form of Artificial Intelligence (AI) tools, such as ChatGPT. Additionally, creating derivatives of ISA IP using AI is also prohibited without express written permission from ISA’s CEO. In the case of such use, ISA will suspend a licensee’s access to ISA IP, and further legal action will be considered. Please review ISA's Terms and Conditions for further information.

  • CCST
ISA Certified Control Systems Technician (CCST) program

Certified Control System Technicians (CCSTs) calibrate, document, troubleshoot, and repair/replace instrumentation for systems that measure and control level, temperature, pressure, flow, and other process variables.

CCST question

In a bubbler (dip tube) level measuring system, for a bubble to be emitted at the open end of the purge pipe, the air pressure at that point is _______ the pressure exerted by the liquid at that point.

A. twice
B. equal to
C. less than
D. three times

CCST Answer
The correct answer is B, "equal to."- In order for air to be discharged from the end of a bubbler purge tube, the air pressure in the tube must be equal to (or higher than) the pressure exerted by the liquid head in the tank.
As the tank level is decreased, the liquid head pressure at the tip of the purge tube decreases, and more bubbles per unit of time can escape. The corresponding reduction in pressure in the purge tube is proportional to the level in the tank.
Therefore, the point at which the liquid head pressure and the purge tube pressure are equal is the highest level (URV = 100%) that the device will measure.

 

Reference: Goettsche, L.D. (Editor), Maintenance of Instruments and Systems, Second Edition, ISA, 2005.

Reader Feedback


We want to hear from you! Please send us your comments and questions about this topic to InTechmagazine@isa.org.



Like This Article?

Subscribe Now!

About The Author